TEMPORARY GROUND CLAMPS FOR HIGH VOLTAGE LINES
| Electrical and
| ![]() | ![]() | ![]() | ![]() | ![]() | |
| Catalog Reference | ||||||
| RC600-1743 | RG3622-1 | RG3622-2 | RC600-0434 | RC600-0065 | ||
| Description | Aluminium body; Smooth jaw; Eyescrew; Cable connection through plain ferrule | Aluminium body; Smooth jaw; Connectors and eyescrew; Cable connection through plain ferrule | Aluminium body; Smooth jaw; Steel clamp for securing the protected cable with a perimeter from 51 to 70 mm; Connectors and eyescrew; Cable connection through plain ferrule | Aluminium body; Serrated jaw; Eyescrew; Cable connection through plain ferrule | Aluminium body; Serrated jaw; Eyescrew; Cable connection through plain ferrule | |
| Rated Current (A) | 400 | 400 | 400 | 400 | 400 | |
| Short-circuit Current (lcc) | 30 cycles (kA) | 30 | 30 | 30 | 30 | 30 |
| 60 cycles (kA) | 23 | 23 | 23 | 23 | 23 | |
| Connection | Maximum | 1000 MCM Cu 1590 MCM CAA Ø 38 mm | 566 MCM Cu 900 MCM CAA Ø 29 mm | 566 MCM Cu 900 MCM CAA Ø 29 mm | 950 MCM Cu 1510 MCM CAA Ø 38 mm | 954 MCM CAA Ø 30 mm |
| Minimum | 6 AWG Cu 4 AWG CA Ø 4 mm | 6 Cu Ø 4 mm | 6 Cu Ø 4 mm | 6 Cu Ø 4 mm | 6 Cu Ø 4 mm | |
| Cable Ferrule (mm²) | Maximum | 95 | 95 | 95 | 95 | 95 |
| Minimum | 16 | 16 | 16 | 16 | 16 | |
| Installation Torque (daN.m) | 3,0 | 3,0 | 3,0 | 3,0 | 3,0 | |
| ASTM Designation | Type I Class A Grade 5 | Type I Class A Grade 5 | Tipo I Classe A Grau 5 | Type I Class B Grade 5 | Type I Class B Grade 5 | |
| Approx. Weight (kg / lb) | 0,72 / 1,59 | 0,72 / 1,59 | 0,76 / 1,68 | 0,92 / 2,03 | 0,52 / 1,15 | |